Construction Does Not Meet Assessed Bushfire Attack Level
I inspected a dwelling in a designated bushfire-prone area and the construction details do not match its assessed Bushfire Attack Level. I typically record timber-framed decks with gaps I can drop a 3mm feeler through, sub-floor and eave vents with standard flyscreen or no screen at all, and external doors with no ember-tight bottom seal. Any of these can admit embers during a bushfire event. Reference: AS 3959.
Causes
- Dwelling predates the BAL classification of the local government area
- Alterations or additions completed without a fresh BAL assessment
- Original BAL specification downgraded on site to reduce construction cost
Symptoms to look for
- Sub-floor and eave vents open or screened with mesh coarser than the 2mm bronze or steel commonly specified for the assessed BAL
- Decking boards with gaps wider than 3mm over combustible subframe close to the house
- External doors with no ember-tight bottom seal or with untreated timber frames exposed
Remedies
- Commission a current BAL assessment and a gap analysis against AS 3959
- Retrofit compliant ember screens, door seals, and non-combustible decking or subframe protection
- Prioritise upgrades on the elevations facing the assessed bushfire hazard