Skip to content
Defect type ·1 observations
Cosmetic · –/5

Gaps around fireplace

Fire safety/real

Gaps around fireplace is a cosmetic fire safety defect SURE inspectors have documented across 1 inspection report.

Causes

  • Improper installation
  • Incomplete finishing
  • Settlement

Symptoms to look for

  • Visible gaps around the perimeter of the fireplace

Remedies

  • Seal or fill the gaps around the fireplace
Watch

Include this check in your next inspection.

Typically a low-severity finding, but worth documenting before maintenance work. Every SURE inspection includes 12 months of free advice.

Inspector-written

Curated entries in Fire safety

All entries →
  • Curated 2–5/5
    Untested Smoke Alarms

    Smoke alarms are sighted but their operational status cannot be confirmed during a standard visual inspection, which does not include functional testing of alarm devices. Western Australian legislation under the Residential Tenancies Act and the Building Act requires interconnected, photoelectric alarms in defined locations; whether the installed units meet that standard remains unverified until tested by a licensed electrician.

  • Curated 2–3/5
    Smoke Alarm Installed Within 3m of Cooking Appliance

    I measured a smoke alarm mounted within three metres of the cooktop, oven, or open kitchen-to-living zone. In my experience this location triggers nuisance alarms from cooking vapours, and occupants respond by disabling or removing the unit. The position also sits inside the kitchen exclusion distance referenced by AS 1670.6.

  • Curated 2–4/5
    Battery-Only Smoke Alarms in Pre-2014 Dwellings

    I found the dwelling relying on 9V or 10-year lithium battery-only smoke alarms rather than 240V hardwired units with battery backup. These were legal at original construction but pre-date the post-May 2014 hardwiring baseline for new Class 1 builds. At inspection I commonly see flat batteries, chirping low-battery signals, or alarms removed entirely.

  • Curated 3–4/5
    Recessed Downlight in Contact With Ceiling Insulation

    From the roof space I observed ceiling insulation laid directly over or against recessed halogen or older LED downlight bodies with no clearance barrier. I have attended ceiling-cavity fires traced to this arrangement in housing from the 1990s and 2000s insulation rollouts, where the trapped fitting heat reached ignition temperatures at the insulation face.

  • Curated 3–5/5
    Heater or Flue Installed Too Close to Combustible Framing

    I measured the clearance from a solid-fuel heater, gas space heater, or flue pipe to adjacent timber studs, joists, or battens and found it below the manufacturer's compliance plate values. Over repeated burn cycles this heat soak can pyrolyse the timber and lower its ignition point. Reference: AS/NZS 2918 for flue clearances. The risk is hidden until charring or smoke appears.

  • Curated 2–3/5
    Ionisation-Type Smoke Alarm Still Installed

    I identified ionisation-chamber smoke alarms in service rather than the photoelectric type now preferred by Queensland, NSW, and WA fire authorities and referenced in AS 3786. In my experience ionisation units respond slowly to smouldering furnishings and bedding, which is the dominant night-time fire scenario, and I recommend replacing them at the ten-year alarm refresh.

Same category

More from Fire safety

All entries →
9,237 inspections
242,618 defects found
30,388 defect types
Local franchise owners
Head office backing

Built to last. Inspected to be SURE.

One inspection, twelve months of advice, and the same person on the other end of the phone every time you call. That is the part you do not see on the brochure.

Same-day reports (subject to access and availability) 12 months free advice Your inspector reads every report
Start my quote
Or call 1300 787 327 business hours support

9,237 inspections · 242,618 defects found · Inspector-owned franchises